E•ENGINEERING
DESK TOOLS
Back to Plant Maintenance

Boilers & steam systems · Project notes

Boiler Burner Start-Up Sequence: What Happens Before the Flame Lights

9 November 2026 · Engineering Desk Tools · 8 min read

The job

This page comes from a burner control panel we documented, wired, programmed and tested for a gas-fired steam boiler. The work ran from the drawings and the field instrument list through panel wiring, PLC logic and the operator panel to signal testing and a full test of the firing sequence. The photos are from that panel.

When a burner refuses to light, or lights and then locks out, the operator usually sees one red lamp. Knowing the order of the start-up sequence tells you which step the burner stopped at, and that tells you which switch, valve or sensor to check first. That is what this page sets out.

Boiler burner operator panel with red, green and amber pilot lamps and selector switches, hand-labelled in English and Urdu
The operator panel: pump, burner and fan selectors (M–OFF–A), low and high water lamps, gas leak and lockout lamps. The operators added the Urdu labels themselves.

The start-up sequence, step by step

The burner moves to the next step only when the feedback for the current step arrives. If the feedback does not arrive in time, the burner control unit stops the sequence and locks out.

Flow diagram of the six steps of the boiler burner start-up sequence, with every safety trip leading to lockout
The six steps in order. A safety trip at any point closes the gas valves and locks the burner out.

1. Blower on and purge

The forced-draught fan starts first. The contactor sends back a run signal, and the air pressure switch must make to prove that air is actually flowing, not just that the motor is energised. The fan then purges the furnace and flue so that no unburnt gas is left from the last firing. The purge time is set by the burner manufacturer and the applicable standard; it is not something to shorten on site.

2. Damper position proven

The modulating motor drives the air damper (and on this burner, the fuel linkage) through its range. Its limit switches tell the logic where it is: fully open for the purge, then back to the low-fire start position for ignition. If the start-position switch never makes, the burner waits here. A slipped linkage or a mis-set cam is the usual cause.

3. Gas valve leak test

Before any gas reaches the burner, the logic checks that the safety shut-off valves are tight. The valves are opened and closed in a set order, and a pressure switch on the pipe section between them has to show that pressure is held, or stays vented, for the test time. If a valve is passing, the pressure changes, the test fails and the burner does not continue. This step is what stops a leaking valve from filling a cold furnace with gas.

4. Pilot valve and ignition

The pilot gas valve opens and the ignition transformer sparks the electrode. This trial for ignition is deliberately short. If no flame is seen before it ends, the pilot closes and the burner locks out rather than trying again on its own.

5. Flame proven, main gas valve opens

The flame sensor (a UV cell on this boiler) has to see the pilot flame and keep holding the flame signal. Only then does the main gas valve open. From here on, the flame signal is supervised continuously: if it is lost, the gas valves close within the safety time of the burner control unit.

6. Firing rate follows steam pressure

Once the main flame is established, the burner is released to modulation. A pressure transmitter on the steam drum sends a 4–20 mA signal, the pressure control loop compares it with the setpoint, and the modulating motor moves the burner between low and high fire. A second loop holds the drum level by controlling the feed water.

Safeties that stop the burner

Each safety is wired so that the safe state is the de-energised state: a broken wire or a lost supply also stops the burner. Every one of them must close the gas valves and hold the burner in lockout until someone resets it.

Safety interlocks on this boiler
SafetySignal fromWhat it protects against
High steam pressurePressure switch on the steam drumPressure above the working limit, before the safety valve has to lift
Drum level low (1st and 2nd low water)Level switches or level transmitterFiring with the tubes uncovered, the most damaging boiler failure
Drum level highLevel switch or level transmitterWater carried over into the steam main
Gas leak / valve leak testPressure switch between the gas valvesGas passing a shut valve into the furnace
Gas pressure low and highGas pressure switches on the gas trainUnstable flame or flame failure from wrong supply pressure
Air pressureAir pressure switch on the fanFiring without combustion air
Flame failureUV flame sensor and burner control unitGas flowing with no flame to burn it
Never jumper out a safety to get the boiler running. If a safety keeps tripping, it is telling you something is wrong. Find the cause, fix it and test the safety again.
Burner control unit with a red lockout lamp mounted above a group of numbered plug-in relays
The burner control unit (top) with its red lockout lamp, and the numbered interposing relays below it. Flame supervision stays with the dedicated burner control unit.

A note on PLCs: the PLC on a job like this runs the sequence, the interlock logic and the operator indications, but the flame supervision belongs to a dedicated burner control unit (flame safeguard) built and certified for that purpose. A general-purpose PLC is not a substitute for it.

Where to look when the burner stops

Note which step the burner reached before it locked out. That narrows the search to a few devices.

Common stopping points and first checks
Stops atLikely causeCheck first
Fan running, no purgeAir pressure switch not madeFan rotation, blocked air inlet, switch setting and sensing tube
Damper positionLimit switch not reachedModulating motor supply (24 V AC here), linkage, cam and switch setting
Leak testValve seat passing or pressure not heldValve seats, vent valve, gas supply pressure, test pressure switch
Ignition trialNo pilot flameElectrode gap and HT lead, pilot gas pressure, pilot valve opening
Just after the main valve opensFlame signal lostUV cell dirty or badly sighted, gas pressure dip, air/fuel ratio
While firingA safety trippedSteam pressure, drum level, gas pressure switches; read the lamp first

Every signal on one sheet

Before the panel was built, every field device was listed against a terminal number. The sheet below became the reference for wiring, loop checks and later fault-finding. It covers the neutral links, the water level switches, the door and air pressure switches, the ignition, pilot, main and vent valve outputs, the gas high and low test switches, the UV flame sensor, the modulating motor limit switches, its 24 V AC supply and 4–20 mA position signal, and the 4–20 mA measurement signals.

Hand-drawn terminal list numbered 1 to 45 showing the boiler burner field signals on each terminal
The field terminal list: 45 terminals, each labelled with the signal it carries. Simple, but it saved hours during signal testing.
How the signals group together
GroupSignals
Water levelLow water, low-low water, high water, feed water pump
Burner provingAir pressure switch, door switch, modulating motor limit switches, UV flame sensor
Gas trainGas low and gas high pressure switches, leak test, main gas valve, bypass valve, vent valve
Ignition and fuelIgnition transformer, pilot valve, main oil valve (dual fuel)
AnalogueModulating motor 4–20 mA, measurement transmitters 4–20 mA
IndicationPanel lamps, alarm bell with test and mute

Scaling and testing those 4–20 mA loops is covered in the 4–20 mA scaling guide, and the loop voltage budget guide explains why a long cable run can stop a loop-powered transmitter from reaching 20 mA.

How the job was run

  1. Documentation first: the field instrument list, terminal drawing, P&ID, panel wiring diagram, electrical drawing and the written sequence of logic.
  2. Panel design and the order to the panel builder.
  3. Panel wiring, with ferrules and labels on every core.
  4. PLC logic built and tested on the bench before it went near the boiler.
  5. Operator interface: HMI screens and the lamp panel.
  6. Field termination into the new panel, terminal by terminal against the list.
  7. Signal testing: every input operated at the device and seen at the panel, every output driven and seen at the device.
  8. Sequence testing: the full start-up run step by step, and each safety tripped on purpose to prove it stops the burner.
Rear of a control panel door showing pilot lamps and selector switch contact blocks wired with red control cable and cable ties
The back of the operator door: each lamp and selector contact block is wired and tied in its own loop, so a single device can be replaced without disturbing the others.

The written sequence of logic is the most useful document of the set. Written in plain steps (what starts, what feedback it waits for, what happens if the feedback never comes), it becomes the PLC specification, the test procedure and the fault-finding guide all at once.

Motor starter section with contactors, electronic overcurrent relays, timers and moulded-case circuit breakers
The power section: contactors and electronic overcurrent relays for the fan, pump and oil pump motors, fed through moulded-case circuit breakers.

Checks before handing the boiler back

  • Run the full start-up at least twice and watch each step happen in order.
  • Trip each safety in turn, following the manufacturer's test method, and confirm the gas valves close and the burner locks out.
  • Confirm that a lockout cannot be cleared just by switching the panel off and on, if the burner control unit is designed that way.
  • Check the lamp for every alarm matches the device that caused it.
  • Record setpoints, switch settings and test results in the maintenance log, with the date and who witnessed the test.

Recording those results is what the free maintenance log templates are for.

Related calculators

This page describes a typical gas burner sequence as set up on one boiler. Timings, test methods and safety settings come from the burner manufacturer and the standards that apply at your site. Follow them, and your site's permit and isolation procedures, for any work on a live boiler.