Instrumentation5 min readUpdated 5 October 2026

4–20 mA scaling: check the transmitter and HMI ranges

Check lower and upper range values, linear scaling and out-of-range signals before interpreting a 4–20 mA reading.

What a 4–20 mA signal represents

A two-wire transmitter regulates loop current in proportion to the measured variable. The lower range value (LRV) is set to 4 mA and the upper range value (URV) to 20 mA, so the 16 mA span carries 0 to 100 percent of the configured range. The live-zero at 4 mA lets a receiver tell a true 0 percent reading from a broken loop, which would read about 0 mA.

Two ranges are involved in every loop: the range configured in the transmitter and the range entered in the PLC, DCS or HMI scaling block. The signal is only interpreted correctly when both are identical. Most wrong readings on commissioned loops come from a mismatch between those two sets of numbers rather than from a faulty instrument.

The scaling formulas

The site calculators assume a linear relationship between current and process value:

  • Process value = LRV + (mA − 4) ÷ 16 × (URV − LRV)
  • mA = 4 + 16 × (PV − LRV) ÷ (URV − LRV)
  • Percent of span = (mA − 4) ÷ 16 × 100

Use 4–20 mA to engineering units to read a signal and engineering units to 4–20 mA to predict one. Both extrapolate outside the range instead of clamping, and the first flags signals below 4 mA or above 20 mA. A square-root flow signal from a differential-pressure transmitter is not linear in flow, so these formulas do not apply to it directly.

Signal (mA)Percent of span0–6 bar range
400.00 bar
8251.50 bar
12503.00 bar
16754.50 bar
201006.00 bar

Worked example 1: reading a pressure transmitter

A pressure transmitter is ranged 0 to 6 bar. A loop calibrator or multimeter in series reads 12.8 mA.

Percent of span = (12.8 − 4) ÷ 16 × 100 = 55 %.

Pressure = 0 + 0.55 × (6 − 0) = 3.30 bar.

Converting with the pressure unit converter (1 bar = 100 kPa, 1 psi ≈ 6.894757 kPa), 3.30 bar is 47.9 psi. Keep gauge and absolute references the same through the conversion; a loop signal does not tell you which one the transmitter measures.

Worked example 2: predicting the signal, and a range mismatch

Prediction. A temperature transmitter is ranged −50 to 150 °C and the process is at 37 °C: mA = 4 + 16 × (37 − (−50)) ÷ 200 = 4 + 16 × 87 ÷ 200 = 10.96 mA.

Mismatch. A transmitter is ranged 0 to 6 bar, but the PLC input is scaled 0 to 10 bar. At a true 3.30 bar the loop carries 12.8 mA and the PLC computes 0 + (12.8 − 4) ÷ 16 × 10 = 5.50 bar. The HMI reading is 1.67 times the true value, the ratio of the two spans. At 4.5 bar actual the loop carries 16.0 mA and the HMI shows 7.50 bar. A ratio that stays constant across the range, with a matching zero, usually points to a span setting error rather than a drift or calibration fault.

Worked example 3: out-of-range and level

A level transmitter is ranged 0 to 3.2 m and the receiver shows 5.6 mA: level = (5.6 − 4) ÷ 16 × 3.2 = 0.32 m, or 10 % of span. That is a valid reading.

If the same loop on a 0–10 bar transmitter reads 3.6 mA, the linear formula gives (3.6 − 4) ÷ 16 × 10 = −0.25 bar (−2.5 % of span). The calculator reports this value and flags the signal as outside 4–20 mA. Treat it as a diagnostic clue, not a measurement: it may be a real slightly negative reading, a zero offset, or a device fault current. Some devices use fixed alarm currents outside the normal band, and the values differ between manufacturers and configurations, so check the device manual.

Common mistakes

  • Assuming the transmitter range from memory instead of reading the configured LRV and URV.
  • Scaling the PLC input 0–100 % and applying a different engineering range elsewhere in the program.
  • Applying the linear formula to a square-root extracted flow signal.
  • Mixing units, for example a 0–6 bar transmitter and a psi display range.
  • Confusing gauge, absolute and differential pressure.
  • Measuring mA with the meter in parallel instead of in series.
  • Treating a value from an out-of-range signal as a trustworthy process reading.

Checks before you trust the result

Check scaling before calibration, because calibration cannot fix a configuration error. Scaling asks whether the numbers in the transmitter and the receiver agree; calibration asks whether the transmitter output is accurate for a known input.

  1. Read LRV, URV and units from the transmitter itself, not from the drawing, and confirm the receiver uses the same pair.
  2. Apply or simulate 4, 12 and 20 mA and see that the display agrees with the table above.
  3. Do a five-point check at 0, 25, 50, 75 and 100 percent of span (4, 8, 12, 16 and 20 mA), rising and then falling, recording the applied input, the measured mA and the displayed value.
  4. Mind resolution: one microamp is 0.0625 % of a 16 mA span, so a meter that resolves only 0.01 mA limits a check to about 0.06 % of span.
  5. Note damping or fault-mode settings that could affect a reading.

Tolerances come from the instrument datasheet or the site procedure, not from this guide.

FAQ

Why does 12 mA mean 50 percent and not 60?

Because the zero is at 4 mA: (12 − 4) ÷ 16 = 0.5. Treating 0 mA as zero is the usual cause of a 25 percent offset in a hand calculation.

Is the calculator result an instrument error?

No. It only converts between mA and engineering units. Error is found by comparing a displayed value with a known applied input.

Can 3.8 mA or 20.5 mA be a normal reading?

Slightly outside the band can occur from a calibration offset or over-range, but investigate rather than accept it.

What if the receiver expects 1–5 V?

A 250 ohm resistor across the loop converts 4–20 mA into 1–5 V (V = 0.004 × 250 = 1 V and 0.020 × 250 = 5 V). The percent-of-span arithmetic is unchanged.

Recording the data

Log the tag, LRV, URV, units, the as-found and as-left readings at each test point, the test equipment and its calibration status, the date and who carried out the test. Record both the transmitter range and the PLC or HMI range in the same row, so a mismatch is visible at a glance. The free calibration record template on the site is laid out for this, and the loop voltage budget calculator helps when a loop will not reach 20 mA because of insufficient supply voltage.