E•ENGINEERING
DESK TOOLS

Engineering tools

42 tools · instant results

INSTRUMENTATION

4–20 mA Scaling Calculator – mA to Engineering Units

Read a linear transmitter signal as pressure, temperature, level or another engineering value.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

Value = LRV + ((mA − 4) / 16) × (URV − LRV).

Linear scaling only. Does not apply directly to square-root extracted flow signals. Out-of-range signals are extrapolated and flagged; consult the device manual for fault thresholds.

Calculation reviewed: 4 October 2026 · Engineering Desk Tools · How we check calculations

4–20 mA scaling formula

Process value = LRV + (mA − 4) ÷ 16 × (URV − LRV)

Percent of span = (mA − 4) ÷ 16 × 100

LRV is the lower range value (the reading at 4 mA) and URV the upper range value (at 20 mA). The span of the signal is 16 mA, so every 1 % of range is 0.16 mA. Example: a 0–10 bar transmitter sending 14.4 mA reads 0 + (14.4 − 4) ÷ 16 × 10 = 6.5 bar.

4–20 mA to percent conversion table

Percent of rangeSignal0–10 bar range−50 to 150 °C range
0 %4.0 mA0 bar-50 °C
10 %5.6 mA1 bar-30 °C
20 %7.2 mA2 bar-10 °C
30 %8.8 mA3 bar10 °C
40 %10.4 mA4 bar30 °C
50 %12.0 mA5 bar50 °C
60 %13.6 mA6 bar70 °C
70 %15.2 mA7 bar90 °C
80 %16.8 mA8 bar110 °C
90 %18.4 mA9 bar130 °C
100 %20.0 mA10 bar150 °C

PLC analog scaling: raw counts to engineering units

A PLC analog input card converts the current to a raw integer. Scale it the same way, using the card's count range instead of 4 and 20 mA:

Value = LRV + (raw − rawmin) ÷ (rawmax − rawmin) × (URV − LRV)

For example, Siemens S7-1200 and S7-1500 analog inputs set to 4–20 mA report 0 at 4 mA and 27,648 at 20 mA, so a raw value of 13,824 is 50 % of range. Other modules use different ranges, such as 0–4,095 or 0–32,767; take the values from the module manual.

Why 4 mA and not 0 mA?

The 4 mA "live zero" lets the system tell a real zero reading from a broken wire or a failed transmitter, which would send 0 mA. It also leaves enough current to power a two-wire transmitter from the loop.

Out-of-range and fault signals (NAMUR NE 43)

NAMUR NE 43 limits. Check the transmitter manual; not every device follows them.
SignalUsual meaning
3.8 to 4.0 mAProcess slightly below range; transmitter still measuring
20.0 to 20.5 mAProcess slightly above range; transmitter still measuring
3.6 mA or lessTransmitter fault (downscale alarm)
21.0 mA or moreTransmitter fault (upscale alarm)
About 0 mAOpen loop, blown fuse or no supply

How to use the 4–20 mA Scaling calculator

Enter the measured loop current in mA and the transmitter range: the lower range value at 4 mA and the upper range value at 20 mA. Select Calculate to read the process value and the percent of span.

Inputs and measurement basis

Method and interpretation

A 4 mA signal corresponds to the lower range value, 20 mA to the upper range, and 12 mA to the midpoint of a linear range. The engineering unit comes from the transmitter configuration. A pressure range, temperature range and level range can use the same arithmetic while producing completely different physical quantities.

Value = LRV + ((mA − 4) / 16) × (URV − LRV).

Linear scaling only. Does not apply directly to square-root extracted flow signals. Out-of-range signals are extrapolated and flagged; consult the device manual for fault thresholds.

Worked example

InputExample value
Measured signal (mA)12
Lower range value (at 4 mA)0
Upper range value (at 20 mA)100

Calculated result: 50 engineering units. 50% of span

Common mistakes

Using a zero-based 0–20 mA formula on a 4–20 mA transmitter; entering an outdated range; applying linear scaling to an unprocessed square-root flow signal.

Frequently asked questions

What is the 4–20 mA formula?

Process value = LRV + (mA − 4) ÷ 16 × (URV − LRV). The reverse is mA = 4 + 16 × (value − LRV) ÷ (URV − LRV).

What is 12 mA in a 4–20 mA signal?

12 mA is 50 % of the range. On a 0–10 bar transmitter it is 5 bar; on a 0–200 °C transmitter it is 100 °C.

How many mA is 1 % of a 4–20 mA signal?

The signal span is 16 mA, so 1 % of range is 0.16 mA and 25 % is 4 mA above the 4 mA zero, which is 8 mA.

How do I scale 4–20 mA in a PLC?

Use Value = LRV + (raw − rawmin) ÷ (rawmax − rawmin) × (URV − LRV), with the raw count range of your analog input card, for example 0 to 27,648 on Siemens S7-1200 and S7-1500.

Does this work for a flow transmitter?

Only if the transmitter output is linear in flow. If the signal is linear in differential pressure, flow is proportional to the square root of the percent of span, so apply square-root extraction first.

What does the result mean?

The result is the process value the transmitter is reporting for the measured current, based on its configured range. A reading outside 4 to 20 mA is extrapolated, so check the device fault thresholds.

Related tools and records

Use related calculations with consistent units, periods and equipment scope.

Embed this calculator

Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.