Calculation reviewed: 4 October 2026 · Engineering Desk Tools · How we check calculations
Engineering units to mA formula
mA = 4 + 16 × (PV − LRV) ÷ (URV − LRV)
mA from percent = 4 + 0.16 × percent
Example: a temperature transmitter ranged −50 to 150 °C reading 25 °C should send 4 + 16 × (25 − (−50)) ÷ 200 = 10 mA. If the loop current differs, check the transmitter range, the wiring and the input card.
Percentage to mA table
Five-point loop check
A common calibration check applies 0, 25, 50, 75 and 100 % of range and records the output at each point, going up and then down. Expected values are 4, 8, 12, 16 and 20 mA. Enter each measured error in the instrument calibration error calculator and record the results in the calibration record template.
How to use the Engineering Units to 4–20 mA
Enter the process value and the transmitter range (the value at 4 mA and at 20 mA), then select Calculate. Use the result as the expected current when you check or simulate a loop.
Inputs and measurement basis
- Process value. Process value in the same unit as the range.
- Lower range value (at 4 mA). Process value at 4 mA from the transmitter configuration.
- Upper range value (at 20 mA). Process value at 20 mA from the transmitter configuration.
Method and interpretation
This inverse calculation is useful when planning loop checks. Enter an engineering value to find the expected transmitter current, then compare that expected current with a measured or simulated value. It does not command a physical output and cannot determine transmitter saturation or diagnostic thresholds without the device documentation.
mA = 4 + 16 × (PV − LRV) / (URV − LRV).
Linear scaling only. Values outside the configured range are extrapolated, not clamped. The result does not represent the physical output limits of a transmitter.
Worked example
Calculated result: 12 mA. Expected linear loop current
Common mistakes
Swapping the lower and upper endpoints; assuming extrapolated current will be produced by the device; mixing units between the process value and the range.
Frequently asked questions
How do you convert a percentage to mA?
mA = 4 + 0.16 × percent. 0 % is 4 mA, 25 % is 8 mA, 50 % is 12 mA, 75 % is 16 mA and 100 % is 20 mA.
What current should a transmitter send at a given reading?
Use mA = 4 + 16 × (reading − LRV) ÷ (URV − LRV) with the configured range. A 0–6 bar transmitter at 3 bar should send 12 mA.
What does the result mean?
The result is the current a linear transmitter should produce for the process value entered. Compare it with a simulated or measured loop current to check the range and wiring.