Amps to kW Calculator – Three Phase & Single Phase

Convert AC line current into electrical input power using voltage and power factor.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

Single-phase: kW = V × I × PF / 1000. Three-phase: kW = √3 × V × I × PF / 1000.

Use RMS voltage and current measured over the same operating condition, with power factor greater than 0 and up to 1. For balanced three-phase supplies, enter line-to-line voltage. The result is electrical input power; motor shaft output also depends on efficiency.

Calculation reviewed: 14 October 2026 · Engineering Desk Tools · How we check calculations

Amps to kW formula

Three-phase: kW = √3 × VL-L × I × PF ÷ 1000

Single-phase: kW = V × I × PF ÷ 1000

DC: kW = V × I ÷ 1000

Amps to kVA formula

Three-phase: kVA = √3 × VL-L × I ÷ 1000

Single-phase: kVA = V × I ÷ 1000

kVA does not need the power factor. Use kVA when you are sizing a transformer, generator or UPS; use kW for energy use and running cost.

Amps to kW and kVA chart

kW columns use a power factor of 0.85. kVA columns do not depend on power factor.
Current400 V 3-ph kW480 V 3-ph kW230 V 1-ph kW400 V 3-ph kVA230 V 1-ph kVA
5 A2.94 kW3.53 kW0.98 kW3.46 kVA1.15 kVA
10 A5.89 kW7.07 kW1.96 kW6.93 kVA2.30 kVA
16 A9.42 kW11.3 kW3.13 kW11.1 kVA3.68 kVA
20 A11.8 kW14.1 kW3.91 kW13.9 kVA4.60 kVA
32 A18.8 kW22.6 kW6.26 kW22.2 kVA7.36 kVA
50 A29.4 kW35.3 kW9.78 kW34.6 kVA11.5 kVA
63 A37.1 kW44.5 kW12.3 kW43.6 kVA14.5 kVA
100 A58.9 kW70.7 kW19.6 kW69.3 kVA23.0 kVA
125 A73.6 kW88.3 kW24.4 kW86.6 kVA28.8 kVA
200 A118 kW141 kW39.1 kW139 kVA46.0 kVA
400 A236 kW283 kW78.2 kW277 kVA92.0 kVA

Amps to kW three phase: quick answers

Three-phase: kW = 1.732 × V × I × PF ÷ 1000

The table gives real power at 0.85 power factor. For three-phase, the voltage is line-to-line and the current is the current in one line, not the sum of all three.

Amps to kW at 0.85 power factor.
Current230 V 1-phase400 V 3-phase415 V 3-phase480 V 3-phase
10 A1.96 kW5.89 kW6.11 kW7.07 kW
16 A3.13 kW9.42 kW9.78 kW11.3 kW
20 A3.91 kW11.8 kW12.2 kW14.1 kW
25 A4.89 kW14.7 kW15.3 kW17.7 kW
32 A6.26 kW18.8 kW19.6 kW22.6 kW
40 A7.82 kW23.6 kW24.4 kW28.3 kW
50 A9.78 kW29.4 kW30.5 kW35.3 kW
63 A12.3 kW37.1 kW38.5 kW44.5 kW
80 A15.6 kW47.1 kW48.9 kW56.5 kW
100 A19.6 kW58.9 kW61.1 kW70.7 kW
125 A24.4 kW73.6 kW76.4 kW88.3 kW
150 A29.3 kW88.3 kW91.6 kW106 kW
200 A39.1 kW118 kW122 kW141 kW
250 A48.9 kW147 kW153 kW177 kW
400 A78.2 kW236 kW244 kW283 kW
630 A123 kW371 kW385 kW445 kW

200 amps to kW

Real power carried by 200 A.
Supply200 A in kW
230 V single-phase, PF 146.0 kW
240 V single-phase, PF 148.0 kW
400 V three-phase, PF 0.85118 kW
415 V three-phase, PF 0.85122 kW
480 V three-phase, PF 0.85141 kW
400 V three-phase, PF 1139 kW

A 200 A breaker or service is not a 200 A continuous load. Many codes limit continuous loads to 80 % of the rating, so plan around 160 A for a load that runs for hours.

How to use the Amps to kW calculator

Choose single-phase or three-phase, enter the measured line current, the supply voltage and the power factor, then select Calculate. Measure current and voltage under the same operating condition.

Inputs and measurement basis

Method and interpretation

The three-phase expression assumes balanced loading and a suitable measured power factor. A simple clamp-meter current reading alone cannot reveal active power. Where harmonic distortion or imbalance is important, a suitable power analyzer is preferable to substituting a guessed power factor. The result describes electrical input, not useful mechanical output.

Single-phase: kW = V × I × PF / 1000. Three-phase: kW = √3 × V × I × PF / 1000.

Use RMS voltage and current measured over the same operating condition, with power factor greater than 0 and up to 1. For balanced three-phase supplies, enter line-to-line voltage. The result is electrical input power; motor shaft output also depends on efficiency.

Worked example

InputExample value
SupplyThree-phase
Line current (A)25
Supply voltage (V)415
Power factor (decimal, up to 1)0.85

Calculated result: 15.2745 kW. Estimated active electrical input power

Common mistakes

Adding three line currents before entering the current; assuming a power factor of one without evidence; interpreting electrical input as shaft output.

Frequently asked questions

How do you convert amps to kW for three phase?

Multiply 1.732 × line-to-line voltage × line current × power factor, then divide by 1000. For 50 A at 400 V and 0.85 PF: 1.732 × 400 × 50 × 0.85 ÷ 1000 = 29.4 kW.

How many kW is 200 amps three phase?

118 kW at 400 V and 0.85 power factor, 122 kW at 415 V and 141 kW at 480 V. At 240 V single-phase and power factor 1, 200 A is 48 kW.

How many kW is 100 amps?

At 400 V three-phase and 0.85 PF, 100 A is 58.9 kW. At 230 V single-phase and power factor 1 it is 23 kW.

How many kW is 32 amps 3 phase?

18.8 kW at 400 V and 0.85 power factor, or 22.2 kW at power factor 1. A 32 A single-phase circuit at 230 V carries 7.36 kW at power factor 1.

How do you convert amps to kW?

Three-phase: kW = 1.732 × volts × amps × power factor ÷ 1000. Single-phase: kW = volts × amps × power factor ÷ 1000. For example, 32 A at 400 V three-phase and PF 0.85 is 18.8 kW.

How do you convert amps to kVA?

Three-phase: kVA = 1.732 × volts × amps ÷ 1000. Single-phase: kVA = volts × amps ÷ 1000. 100 A at 400 V three-phase is 69.3 kVA.

Why do I need the power factor for amps to kW?

Current and voltage give apparent power (kVA). Only part of it is real power (kW), and the power factor is that fraction. Without a measured value, 0.8 to 0.9 is typical for loaded motors.

What does the result mean?

The result is the estimated active electrical input power for the measured current, voltage and power factor. It is not the shaft output of a motor: efficiency separates the two.

Related tools and records

Use related calculations with consistent units, periods and equipment scope.