E•ENGINEERING
DESK TOOLS

Engineering tools

42 tools · instant results

MECHANICAL

Compressed Air Receiver Size Calculator

Size an air receiver to supply a peak demand for a set time within an allowable pressure drop.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

Receiver volume (m³) = shortfall flow × time × atmospheric pressure / allowable pressure drop. Atmospheric pressure is taken as 1.01325 bar.

The flow is the demand that the compressor cannot supply during the event, in free-air units. The pressure drop is the usable difference between the compressor loading pressure and the minimum pressure the process needs. The calculation assumes constant temperature (isothermal) and does not size for compressor control, cycling or leakage. Add margin and confirm the receiver pressure rating, drain and relief requirements.

Method: standard dimensional arithmetic; equation and input units shown above.

Calculation reviewed: 14 October 2026 · Engineering Desk Tools · How we check calculations

This air receiver sizing calculator finds the tank volume needed to supply a short peak in compressed air demand, or a short compressor stop, while the system pressure falls no more than an allowed amount.

Air receiver sizing formula

V (m³) = Q × t × Patm ÷ ΔP

Q is the air demand the compressor cannot supply during the event (m³/min of free air), t is how long the event lasts (minutes), Patm is atmospheric pressure (1.013 bar) and ΔP is the allowed pressure fall in the receiver (bar).

Example: a blow-off nozzle needs an extra 2 m³/min for 1.5 minutes, and pressure may fall from 7.5 to 6.5 bar g (ΔP = 1 bar). V = 2 × 1.5 × 1.013 ÷ 1 = 3.04 m³, so a 3,000 to 3,500 litre receiver.

Receiver size table

Receiver volume in litres, isothermal calculation. Round up to the next standard tank size.
Shortfall30 s, ΔP 1 bar1 min, ΔP 1 bar2 min, ΔP 1 bar1 min, ΔP 0.5 bar
1 m³/min507 L1,013 L2,026 L2,026 L
2 m³/min1,013 L2,026 L4,053 L4,053 L
5 m³/min2,533 L5,066 L10,132 L10,132 L
10 m³/min5,066 L10,132 L20,265 L20,265 L

Rules of thumb

Many compressor suppliers give a quick sizing rule based on compressor output, often in the range of about 1 to 3 US gallons per cfm (roughly 8 to 25 litres per l/s), with the higher end for load/unload compressors to limit cycling. These rules size for compressor control, not for a known peak demand; use the formula above for peaks and follow the compressor maker's advice for control storage.

Wet and dry receivers

Every receiver needs an automatic drain, a pressure gauge and a safety relief valve, and must be rated for the system pressure under the local pressure vessel rules.

How to use the air receiver sizing calculator

Enter the demand the compressor cannot cover (m³/min free air), how long it lasts in minutes and the pressure fall you can accept in bar. Select Calculate to see the receiver volume. Leaks also drain receivers; check them with the compressed air leak cost calculator.

Frequently asked questions

How do you calculate air receiver size?

V = Q × t × 1.013 ÷ ΔP, with Q in m³/min free air, t in minutes and ΔP in bar. The result is in m³; multiply by 1000 for litres.

What size air receiver do I need for my compressor?

For compressor control, follow the maker's guide, often about 1 to 3 US gallons per cfm. For peak demand, use the formula with the actual shortfall, duration and allowed pressure drop.

Does a bigger receiver save energy?

It can, by reducing compressor cycling and letting the compressor run at a lower pressure band. It does not replace fixing leaks or reducing demand.

What is the difference between a wet and dry receiver?

A wet receiver is before the dryer and collects condensate; a dry receiver is after the dryer and feeds large intermittent users.

Related tools and records

Use related calculations with consistent units, periods and equipment scope.

Embed this calculator

Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.