E•ENGINEERING
DESK TOOLS

Engineering tools

42 tools · instant results

ELECTRICAL

Voltage Drop Calculator – Copper & Aluminium Cable

Estimate cable voltage drop, percentage drop and load-end voltage for copper or aluminium conductors.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

ρ(T) = ρ20 × (1 + α × (T − 20)); R = ρ(T) × length / area. Single-phase drop = 2 × I × R. Three-phase drop = √3 × I × R. Drop (%) = drop / supply voltage × 100. Copper: ρ20 = 0.017241 Ω·mm²/m, α = 0.00393 per °C. Aluminium: ρ20 = 0.028264 Ω·mm²/m, α = 0.00403 per °C.

Enter the one-way length from source to load. The result is resistive drop only: conductor reactance, power factor, parallel cables, harmonics and voltage drop during motor starting are not included, and reactance becomes more important in larger cables. Three-phase voltage is line-to-line. The permitted drop depends on the applicable code, equipment tolerance and project specification. This is not a cable size or protection recommendation.

Calculation reviewed: 4 October 2026 · Engineering Desk Tools · How we check calculations

What is voltage drop?

Voltage drop is the voltage lost along a cable because the conductor has resistance. The longer the cable and the higher the current, the larger the drop, and the lower the voltage at the load. Too much drop makes motors run hot and start slowly, makes lights dim, and can trip sensitive equipment.

Voltage drop formula

Single-phase: Vd = 2 × I × R × L

Three-phase: Vd = √3 × I × R × L

Voltage drop (%) = Vd ÷ supply voltage × 100

I is the load current, L the one-way length and R the conductor resistance per unit length. The factor 2 counts the outgoing and return conductors; √3 (1.732) applies to a balanced three-phase circuit with line-to-line voltage. This calculator works out R from the conductor size and temperature: R = ρ × L ÷ A, with ρ for copper 0.017241 Ω·mm²/m at 20 °C.

Voltage drop formula in AWG (circular mils)

Single-phase: Vd = 2 × K × I × L ÷ CM

Three-phase: Vd = 1.732 × K × I × L ÷ CM

L is the one-way length in feet, CM the conductor area in circular mils, and K the resistivity constant: about 12.9 Ω·cmil/ft for copper and 21.2 for aluminium at 75 °C.

How to calculate voltage drop: worked examples

Metric, three-phase: a 400 V motor feeder carries 32 A over 80 m of 6 mm² copper at 70 °C.

StepCalculationResult
Resistivity at 70 °C0.017241 × (1 + 0.00393 × 50)0.02063 Ω·mm²/m
Conductor resistance0.02063 × 80 ÷ 60.275 Ω
Voltage drop1.732 × 32 × 0.27515.2 V
Percentage15.2 ÷ 400 × 1003.8 %

US, single-phase: a 120 V circuit carries 20 A over 100 ft (one way). The table shows how the conductor size changes the drop.

Copper sizeArea (cmil)Voltage dropDrop at 120 V
12 AWG6,5307.90 V6.6 %
10 AWG10,3804.97 V4.1 %
8 AWG16,5103.13 V2.6 %

A 480 V three-phase feeder carrying 50 A over 200 ft of 6 AWG copper (26,240 cmil) drops 1.732 × 12.9 × 50 × 200 ÷ 26,240 = 8.52 V, or 1.8 %. To use this calculator with AWG sizes, convert to mm²: 12 AWG = 3.31 mm², 10 AWG = 5.26 mm², 8 AWG = 8.37 mm², 6 AWG = 13.3 mm².

Maximum allowable voltage drop

Typical recommended limits. Your project specification or local code may be stricter.
RuleLighting / branch circuitOther uses / total
NEC (US) informational notes 210.19 and 215.23 % on a branch circuit5 % feeder plus branch circuit
IEC 60364-5-52 / BS 7671, public LV supply3 % lighting5 % other uses
IEC 60364-5-52, private LV supply (own transformer)6 % lighting8 % other uses

The NEC figures are recommendations, not mandatory requirements, but many specifications adopt them. Motor starting causes a much larger short-term drop than running current; check it separately for long feeders.

How to use the Voltage Drop calculator

Choose the supply type and conductor material, then enter the load current, the one-way cable length in metres, the conductor size in mm², the supply voltage and the conductor temperature. The calculator returns the voltage drop in volts and percent and the voltage at the load.

Inputs and measurement basis

Method and interpretation

Conductor resistance rises with temperature, so a cable at its operating temperature drops more voltage than a cold one. The calculator corrects the 20 °C resistivity to the temperature you enter. For three-phase the √3 factor converts the per-conductor drop to the line-to-line drop; for single-phase the current flows out and back, so the factor is 2. In larger cables conductor reactance adds to the resistive drop, and a lagging power factor makes it matter more, so use manufacturer impedance data for big feeders.

ρ(T) = ρ20 × (1 + α × (T − 20)); R = ρ(T) × length / area. Single-phase drop = 2 × I × R. Three-phase drop = √3 × I × R. Drop (%) = drop / supply voltage × 100. Copper: ρ20 = 0.017241 Ω·mm²/m, α = 0.00393 per °C. Aluminium: ρ20 = 0.028264 Ω·mm²/m, α = 0.00403 per °C.

Enter the one-way length from source to load. The result is resistive drop only: conductor reactance, power factor, parallel cables, harmonics and voltage drop during motor starting are not included, and reactance becomes more important in larger cables. Three-phase voltage is line-to-line. The permitted drop depends on the applicable code, equipment tolerance and project specification. This is not a cable size or protection recommendation.

Worked example

InputExample value
SupplyThree-phase
Conductor materialCopper
Load current (A)32
One-way cable length (m)50
Conductor cross-section (mm²)6
Supply voltage (V)400
Conductor operating temperature (°C)70

Calculated result: 2.382 % voltage drop. Resistive drop only. Reactance, power factor and starting current are not included. Compare the percentage with the limit in your applicable code or project specification.

Quick-reference table

Three-phase copper cable at 70 °C: 32 A, 50 m one way, 400 V. Resistive drop only; not a cable selection.
Conductor sizeVoltage drop
1.5 mm²38.1122 V (9.5281 %)
2.5 mm²22.8673 V (5.7168 %)
4 mm²14.2921 V (3.573 %)
6 mm²9.5281 V (2.382 %)
10 mm²5.7168 V (1.4292 %)
16 mm²3.573 V (0.8933 %)
25 mm²2.2867 V (0.5717 %)
35 mm²1.6334 V (0.4083 %)
50 mm²1.1434 V (0.2858 %)
70 mm²0.8167 V (0.2042 %)
95 mm²0.6018 V (0.1504 %)

These are illustrative values, not certified ratings or manufacturer data. Use the form for your own conditions.

Common mistakes

Entering the total (out and back) length instead of the one-way length; mixing mm² and AWG sizes; forgetting that a three-phase limit is expressed against line-to-line voltage; judging a cable by the drop at running current when starting current may cause a deeper dip.

Frequently asked questions

What is the formula for voltage drop?

Single-phase: Vd = 2 × I × R × L. Three-phase: Vd = 1.732 × I × R × L, where I is current, L the one-way length and R the conductor resistance per unit length. Divide by the supply voltage and multiply by 100 for percent.

How do you calculate voltage drop in AWG?

Use Vd = 2 × K × I × L ÷ CM for single-phase or 1.732 × K × I × L ÷ CM for three-phase. K is about 12.9 for copper and 21.2 for aluminium, L is one-way feet and CM is the wire area in circular mils.

What is the maximum allowable voltage drop?

The NEC recommends no more than 3 % on a branch circuit and 5 % in total. IEC 60364 and BS 7671 use 3 % for lighting and 5 % for other loads on a public low-voltage supply.

Should I use one-way or round-trip length?

Enter the one-way length from the source to the load. The formula already includes the return path with the factor 2 for single-phase or 1.732 for three-phase.

How can I reduce voltage drop?

Use a larger conductor, shorten the run, move the supply closer to the load, split the load, or use a higher supply voltage. Copper has lower drop than aluminium of the same size.

What does the result mean?

The result is the voltage lost along the cable at the entered current, as volts and as a percentage of the supply. Compare the percentage with the limit in your code or specification, and check the load-end voltage against the equipment tolerance.

Related tools and records

Use related calculations with consistent units, periods and equipment scope.

Embed this calculator

Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.