This motor current calculator estimates the line current a motor draws from its shaft output power, efficiency and power factor. Use it to check a nameplate, compare with a clamp-meter reading or estimate the current of a motor whose nameplate is missing.
Motor current formula
Input kW = shaft kW ÷ efficiency
Three-phase: I = input kW × 1000 ÷ (1.732 × V × PF)
Single-phase: I = input kW × 1000 ÷ (V × PF)
Example: a 15 kW motor at 400 V with 92 % efficiency and power factor 0.86. Input = 15 ÷ 0.92 = 16.3 kW. Current = 16,300 ÷ (1.732 × 400 × 0.86) = 27.4 A.
Estimated full load current table
Why the real current can differ
- Load: at part load the current falls, but not in proportion, because the magnetising current stays almost constant.
- Speed: 2-pole motors usually have a higher power factor, and 6- or 8-pole motors a lower one, than the 4-pole values in the table.
- Supply voltage: a lower voltage gives a higher current for the same load.
- Starting: direct-on-line starting current is typically 6 to 8 times full load current for a few seconds. This calculator gives running current only.
How to use the motor current calculator
Choose three-phase or single-phase, then enter the shaft output power in kW, the efficiency in percent, the power factor as a decimal and the supply voltage. Take efficiency and power factor from the nameplate or data sheet at the load you want to check.
If you know the electrical input power instead of shaft power, use the kW to amps calculator. To convert hp ratings, use the HP to kW converter.
Frequently asked questions
How do you calculate motor full load current?
Divide shaft kW by efficiency to get input kW, then for three-phase divide input watts by 1.732 × voltage × power factor. For 7.5 kW, 90 % efficiency, PF 0.85 at 400 V: 8,333 ÷ (1.732 × 400 × 0.85) = 14.2 A.
What is the full load current of a 7.5 kW motor at 400 V?
About 14 to 15 A for a typical 4-pole motor. Check the nameplate for the exact value.
What is the full load current of a 1 hp motor?
A 1 hp (0.75 kW) three-phase motor at 400 V draws about 1.8 to 2 A. On 230 V single-phase it is around 5 to 7 A, depending on the motor design.
Why is my measured motor current lower than the nameplate?
The motor is probably running below full load. Nameplate current applies at rated output, voltage and frequency.
How much current does a motor draw at start?
Direct-on-line starting current is typically 6 to 8 times the full load current. Star-delta starting reduces it to about one third of that.