E•ENGINEERING
DESK TOOLS

Engineering tools

42 tools · instant results

ELECTRICAL

Short Circuit Current Calculator – Transformer Fault Current

Estimate the prospective three-phase fault current at a transformer secondary from kVA, voltage and impedance.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

Rated current = kVA × 1000 / (√3 × V). Prospective fault current Isc = rated current × 100 / Z%. Fault level (MVA) = kVA / (Z% × 10).

This assumes an infinitely strong upstream supply and ignores cable and busbar impedance, motor contribution and arc resistance, so the real fault current is lower at a downstream point and motor contribution can add to it. It is an estimate of the maximum at the transformer terminals, not a protection study. Use a complete short-circuit study for equipment ratings.

Calculation reviewed: 14 October 2026 · Engineering Desk Tools · How we check calculations

This short circuit current calculator estimates the prospective three-phase fault current at the secondary terminals of a transformer from its kVA rating, secondary voltage and percentage impedance. It is the first number you need when checking the breaking capacity (kA rating) of switchgear near the transformer.

Short circuit current formula

Full-load current IFL = kVA × 1000 ÷ (1.732 × V)

Short-circuit current Isc = IFL × 100 ÷ Z %

Fault level (MVA) = kVA ÷ (Z % × 10)

Example: a 1000 kVA, 400 V transformer with 5 % impedance has a full-load current of 1443 A. The short-circuit current is 1443 × 100 ÷ 5 = 28,868 A, or 28.9 kA. The fault level is 1000 ÷ 50 = 20 MVA.

This assumes an infinite source: the upstream network has zero impedance. That gives the highest possible current at the transformer terminals, which is the safe side for checking breaker kA ratings.

Transformer fault current table

Upper-bound three-phase fault current at the transformer terminals, infinite source. Impedance values are the IEC 60076-5 minimums (4 % up to 630 kVA, 5 % to 1250 kVA, 6 % to 2500 kVA). Use the nameplate impedance for your transformer.
RatingZ %IFL 400 VIsc 400 VIFL 480 VIsc 480 VFault level
100 kVA4.0 %144 A3.6 kA120 A3.0 kA2.5 MVA
250 kVA4.0 %361 A9.0 kA301 A7.5 kA6.2 MVA
315 kVA4.0 %455 A11.4 kA379 A9.5 kA7.9 MVA
500 kVA4.0 %722 A18.0 kA601 A15.0 kA12.5 MVA
630 kVA4.0 %909 A22.7 kA758 A18.9 kA15.8 MVA
800 kVA5.0 %1,155 A23.1 kA962 A19.2 kA16.0 MVA
1,000 kVA5.0 %1,443 A28.9 kA1,203 A24.1 kA20.0 MVA
1,250 kVA5.0 %1,804 A36.1 kA1,504 A30.1 kA25.0 MVA
1,600 kVA6.0 %2,309 A38.5 kA1,925 A32.1 kA26.7 MVA
2,000 kVA6.0 %2,887 A48.1 kA2,406 A40.1 kA33.3 MVA
2,500 kVA6.0 %3,608 A60.1 kA3,007 A50.1 kA41.7 MVA

Why the real fault current can be different

For final breaker and busbar ratings, use a full short-circuit study to IEC 60909 or IEEE 551 that includes all of these.

How to use the Short Circuit Current calculator

Enter the transformer kVA rating, the secondary line-to-line voltage and the percentage impedance from the transformer nameplate. Select Calculate to see the full-load current, the prospective short-circuit current in kA and the fault level in MVA.

Inputs and measurement basis

Method and interpretation

At the transformer secondary, the maximum fault current is limited mainly by the transformer impedance, shown as a percentage on the nameplate. With an infinitely strong supply the fault current equals rated current divided by the per-unit impedance, so a 5 percent impedance gives twenty times rated current. Cable and busbar impedance lower the value farther downstream, while running motors can add current.

Rated current = kVA × 1000 / (√3 × V). Prospective fault current Isc = rated current × 100 / Z%. Fault level (MVA) = kVA / (Z% × 10).

This assumes an infinitely strong upstream supply and ignores cable and busbar impedance, motor contribution and arc resistance, so the real fault current is lower at a downstream point and motor contribution can add to it. It is an estimate of the maximum at the transformer terminals, not a protection study. Use a complete short-circuit study for equipment ratings.

Worked example

InputExample value
Transformer rating (kVA)1000
Secondary line voltage (V)400
Transformer impedance (%)5

Calculated result: 28.8675 kA prospective fault current. Upper-bound estimate at the transformer terminals. Verify equipment short-circuit ratings with a full study.

Common mistakes

Using the primary voltage; entering impedance as a decimal instead of a percentage; treating the transformer-terminal value as the fault level at every downstream board; using this estimate to rate equipment without a full study.

Frequently asked questions

How do you calculate the short circuit current of a transformer?

Find the full-load current (kVA × 1000 ÷ (1.732 × V)) and divide it by the per-unit impedance (Z % ÷ 100). For 500 kVA, 400 V and 4 %: 722 A ÷ 0.04 = 18.0 kA.

What is the fault current of a 1000 kVA transformer?

With 5 % impedance it is about 28.9 kA at 400 V, 27.8 kA at 415 V and 24.1 kA at 480 V. With 5.75 % impedance at 480 V it is 20.9 kA.

What does transformer impedance % mean?

It is the percentage of rated voltage that would drive full-load current through the shorted secondary. A 5 % impedance transformer lets through 100 ÷ 5 = 20 times its full-load current in a bolted fault.

What is fault level in MVA?

It is √3 × voltage × fault current. For a transformer on an infinite source it equals the rating divided by the per-unit impedance: 1000 kVA at 5 % is 20 MVA.

How do I choose the breaker kA rating?

The breaking capacity of the breaker must be at least the prospective short-circuit current at the point where it is installed. Use this calculator as an upper-bound check and confirm with a full study.

What does the result mean?

The result is the highest three-phase fault current at the transformer secondary with an infinitely strong supply. Points downstream see less, and equipment must be rated above the real fault level from a full study.

Related tools and records

Use related calculations with consistent units, periods and equipment scope.

Embed this calculator

Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.