kVA to kW Calculator – and kW to kVA

Convert apparent power (kVA) to real power (kW), or kW to kVA, using the power factor. Also shows reactive power (kVAR).

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

kW = kVA × PF. kVA = kW ÷ PF. Reactive power kVAR = √(kVA² − kW²).

Enter power factor as a decimal between 0 and 1, for example 0.8 for a generator rating. The conversion is the same for single-phase and three-phase. Harmonic distortion is not included.

Calculation reviewed: 14 October 2026 · Engineering Desk Tools · How we check calculations

This kVA to kW calculator converts apparent power (kVA) to real power (kW) and back again, using the power factor. It also shows the reactive power (kVAR), so you can see the full power triangle. Use it for generators, transformers, UPS units and any load that has a kVA rating on the nameplate.

kVA to kW formula

kW = kVA × PF

PF is the power factor, written as a decimal (0.8, not 80 %). Example: a 100 kVA generator at 0.8 power factor gives 100 × 0.8 = 80 kW. A 500 kVA transformer feeding a load at 0.9 power factor can deliver 450 kW.

kW to kVA formula

kVA = kW ÷ PF

Example: a 75 kW load at 0.85 power factor needs 75 ÷ 0.85 = 88.2 kVA of supply capacity. Use this when you know the real load in kW and need to size a generator, transformer or UPS, which are all rated in kVA.

kVA vs kW: what is the difference?

The power triangle: kVA² = kW² + kVAR².
QuantityUnitWhat it meansFormula
Real (active) powerkWPower that does useful work: turns the shaft, heats the elementkW = kVA × PF
Apparent powerkVATotal power the supply has to carry, set by voltage × currentkVA = kW ÷ PF
Reactive powerkVARPower that builds magnetic fields in motors and transformers, then returns to the supplykVAR = √(kVA² − kW²)
Power factor–Ratio of real power to apparent power, from 0 to 1PF = kW ÷ kVA

kVA is always equal to or larger than kW. They are equal only when the power factor is 1, which is true for purely resistive loads such as heaters. Motors, transformers and fluorescent lighting draw reactive current, so for them kW is lower than kVA.

kVA to kW conversion chart

Real power in kW for common kVA ratings. kW = kVA × power factor.
kVAPF 0.8PF 0.85PF 0.9PF 0.95PF 1.0
1 kVA0.80 kW0.85 kW0.90 kW0.95 kW1.00 kW
5 kVA4.00 kW4.25 kW4.50 kW4.75 kW5.00 kW
10 kVA8.00 kW8.50 kW9.00 kW9.50 kW10.0 kW
15 kVA12.0 kW12.8 kW13.5 kW14.2 kW15.0 kW
20 kVA16.0 kW17.0 kW18.0 kW19.0 kW20.0 kW
25 kVA20.0 kW21.2 kW22.5 kW23.8 kW25.0 kW
30 kVA24.0 kW25.5 kW27.0 kW28.5 kW30.0 kW
50 kVA40.0 kW42.5 kW45.0 kW47.5 kW50.0 kW
63 kVA50.4 kW53.5 kW56.7 kW59.8 kW63.0 kW
70 kVA56.0 kW59.5 kW63.0 kW66.5 kW70.0 kW
75 kVA60.0 kW63.8 kW67.5 kW71.2 kW75.0 kW
100 kVA80.0 kW85.0 kW90.0 kW95.0 kW100 kW
125 kVA100 kW106 kW112 kW119 kW125 kW
160 kVA128 kW136 kW144 kW152 kW160 kW
200 kVA160 kW170 kW180 kW190 kW200 kW
250 kVA200 kW212 kW225 kW238 kW250 kW
315 kVA252 kW268 kW284 kW299 kW315 kW
400 kVA320 kW340 kW360 kW380 kW400 kW
500 kVA400 kW425 kW450 kW475 kW500 kW
630 kVA504 kW536 kW567 kW598 kW630 kW
750 kVA600 kW638 kW675 kW712 kW750 kW
800 kVA640 kW680 kW720 kW760 kW800 kW
1,000 kVA800 kW850 kW900 kW950 kW1,000 kW
1,250 kVA1,000 kW1,062 kW1,125 kW1,188 kW1,250 kW
1,500 kVA1,200 kW1,275 kW1,350 kW1,425 kW1,500 kW
2,000 kVA1,600 kW1,700 kW1,800 kW1,900 kW2,000 kW
2,500 kVA2,000 kW2,125 kW2,250 kW2,375 kW2,500 kW

kW to kVA conversion chart

Apparent power in kVA needed for a given kW load. kVA = kW ÷ power factor.
kWPF 0.8PF 0.85PF 0.9PF 0.95
1 kW1.25 kVA1.18 kVA1.11 kVA1.05 kVA
5 kW6.25 kVA5.88 kVA5.56 kVA5.26 kVA
7.5 kW9.38 kVA8.82 kVA8.33 kVA7.89 kVA
10 kW12.5 kVA11.8 kVA11.1 kVA10.5 kVA
15 kW18.8 kVA17.6 kVA16.7 kVA15.8 kVA
22 kW27.5 kVA25.9 kVA24.4 kVA23.2 kVA
30 kW37.5 kVA35.3 kVA33.3 kVA31.6 kVA
37 kW46.2 kVA43.5 kVA41.1 kVA38.9 kVA
45 kW56.2 kVA52.9 kVA50.0 kVA47.4 kVA
55 kW68.8 kVA64.7 kVA61.1 kVA57.9 kVA
75 kW93.8 kVA88.2 kVA83.3 kVA78.9 kVA
90 kW112 kVA106 kVA100 kVA94.7 kVA
110 kW138 kVA129 kVA122 kVA116 kVA
132 kW165 kVA155 kVA147 kVA139 kVA
160 kW200 kVA188 kVA178 kVA168 kVA
200 kW250 kVA235 kVA222 kVA211 kVA
250 kW312 kVA294 kVA278 kVA263 kVA
315 kW394 kVA371 kVA350 kVA332 kVA
400 kW500 kVA471 kVA444 kVA421 kVA
500 kW625 kVA588 kVA556 kVA526 kVA

Generator kVA to kW (0.8 power factor)

Diesel generator sets are normally rated in kVA at a power factor of 0.8 lagging, which is the rating basis used in ISO 8528-1. So the kW rating of a generator is its kVA rating × 0.8. A 500 kVA generator is a 400 kW generator. The table also shows the full-load current, which you can check with the kVA to amps calculator.

Three-phase generator ratings. Check whether the rating is standby, prime or continuous; each has a different allowed load.
Generator ratingkW at 0.8 PFFull-load current 400 VFull-load current 415 VFull-load current 480 V
20 kVA16.0 kW28.9 A27.8 A24.1 A
30 kVA24.0 kW43.3 A41.7 A36.1 A
45 kVA36.0 kW65.0 A62.6 A54.1 A
62.5 kVA50.0 kW90.2 A87.0 A75.2 A
82.5 kVA66.0 kW119 A115 A99.2 A
100 kVA80.0 kW144 A139 A120 A
125 kVA100 kW180 A174 A150 A
160 kVA128 kW231 A223 A192 A
200 kVA160 kW289 A278 A241 A
250 kVA200 kW361 A348 A301 A
320 kVA256 kW462 A445 A385 A
380 kVA304 kW548 A529 A457 A
500 kVA400 kW722 A696 A601 A
750 kVA600 kW1,083 A1,043 A902 A
1,000 kVA800 kW1,443 A1,391 A1,203 A
1,250 kVA1,000 kW1,804 A1,739 A1,504 A
1,500 kVA1,200 kW2,165 A2,087 A1,804 A
2,000 kVA1,600 kW2,887 A2,782 A2,406 A
2,500 kVA2,000 kW3,608 A3,478 A3,007 A

Single-phase and three-phase

The kVA to kW formula is the same for single-phase and three-phase supplies, because both kVA and kW already describe total power. The number of phases only matters when you go to current: use the kW to amps calculator or the kVA to amps calculator for that step.

How to use the kVA to kW calculator

Choose the direction (kVA to kW, or kW to kVA), enter the power value and enter the power factor as a decimal between 0 and 1. Select Calculate. The result shows real power, apparent power and reactive power together. If you do not know the power factor, take it from the equipment nameplate or a power analyser reading; use 0.8 for a generator rating.

Inputs and measurement basis

Method and interpretation

The calculator multiplies or divides by the power factor, then finds reactive power from the power triangle: kVAR = √(kVA² − kW²). Harmonic currents are not included; on loads with drives or rectifiers, the true power factor from a power analyser can be lower than the displacement power factor.

Worked example

A 250 kVA transformer supplies a plant with an average power factor of 0.85. Real power capacity = 250 × 0.85 = 212.5 kW. Reactive power = √(250² − 212.5²) = 131.7 kVAR. If power factor correction raises the power factor to 0.95, the same transformer can carry 237.5 kW, an extra 25 kW, without exceeding its kVA rating. See the power factor correction calculator for the capacitor kVAR.

Common mistakes

Frequently asked questions

How do you convert kVA to kW?

Multiply kVA by the power factor: kW = kVA × PF. For example, 100 kVA at 0.8 power factor is 80 kW.

How do you convert kW to kVA?

Divide kW by the power factor: kVA = kW ÷ PF. For example, 80 kW at 0.8 power factor is 100 kVA, and 75 kW at 0.85 is 88.2 kVA.

How many kW is 1 kVA?

1 kVA is 0.8 kW at 0.8 power factor, 0.85 kW at 0.85 and 0.9 kW at 0.9. It is 1 kW only when the power factor is 1, as with a resistive heater.

How many kVA is 1 kW?

1 kW needs 1.25 kVA at 0.8 power factor, 1.18 kVA at 0.85 and 1.11 kVA at 0.9.

How do you calculate kVAR from kW and kVA?

Use the power triangle: kVAR = √(kVA² − kW²). For 100 kVA and 80 kW, kVAR = √(10,000 − 6,400) = 60 kVAR.

What is 70 kVA in kW?

56 kW at 0.8 power factor, 59.5 kW at 0.85 and 63 kW at 0.9.

How many kW is a 125 kVA generator?

100 kW at the standard 0.8 generator power factor. A 62.5 kVA set is 50 kW and an 82.5 kVA set is 66 kW.

How do you convert HP to kVA?

kVA = HP × 0.746 ÷ (motor efficiency × power factor). A 10 HP motor with 90 % efficiency and 0.85 power factor needs 10 × 0.746 ÷ (0.9 × 0.85) = 9.75 kVA. Use the HP to kW calculator for the first step.

How many kW is a 100 kVA generator?

80 kW. Generators are rated at 0.8 power factor, so kW = 100 × 0.8. Check whether the 100 kVA figure is a standby or prime rating.

What is 500 kVA in kW?

400 kW at 0.8 power factor, 425 kW at 0.85 and 450 kW at 0.9. At 400 V three-phase, 500 kVA is a full-load current of about 722 A.

What is 1000 kVA in kW?

800 kW at 0.8 power factor, 850 kW at 0.85 and 900 kW at 0.9.

Is the kVA to kW formula different for three-phase?

No. kW = kVA × PF for both single-phase and three-phase. The phase only matters when you convert power to current.

What power factor should I use?

Use the nameplate or a measured value. Generator ratings use 0.8. Loaded induction motors are often between 0.8 and 0.9, and resistive heaters are close to 1. Lightly loaded motors can be much lower.

Why are generators and transformers rated in kVA and not kW?

Their heating depends on the current and voltage they carry, not on how much of that power does useful work. The manufacturer does not know the power factor of your load, so the rating is given in kVA.

Is this a final design or equipment approval?

No. The result is a conversion for planning and checking. Confirm generator, transformer and UPS sizing with the manufacturer data, including motor starting, harmonics and site conditions.