Wire Size Calculator (AWG) – Amps, Voltage Drop & NEC Chart

Find the AWG or kcmil wire size for a load in amps or watts using NEC Table 310.16 ampacity, temperature and bundling factors, and a voltage drop check.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

I = W ÷ (V × PF) single-phase, W ÷ (√3 × V × PF) three-phase. Required ampacity = I × 1.25 for continuous loads. Allowed ampacity = smaller of [Table 310.16 value at the insulation rating × temperature factor × bundling factor] and [Table 310.16 value at the terminal rating], and not more than the 240.4(D) limits for 14–10 AWG. Voltage drop = k × K × I × L ÷ CM with k = 2 (single-phase) or √3 (three-phase), K = 12.9 (copper) or 21.2 (aluminum) Ω·cmil/ft, L in feet, CM in circular mils.

Ampacities from NEC Table 310.16 (not more than three current-carrying conductors, 30 °C / 86 °F); temperature factors from Table 310.15(B)(1) and bundling factors from 310.15(C)(1). Wire is limited by its terminations: equipment up to 100 A is often rated for 60 °C unless marked 75 °C. Dwelling services and main feeders may use the 83 % rule in 310.12, which this calculator does not apply. Voltage drop uses DC resistance at 75 °C; reactance is ignored, which is fine for most building wire. Always confirm with your local code and the authority having jurisdiction.

Data reviewed: 20 October 2026 · Engineering Desk Tools · How we check calculations

How to size wire for amps (NEC method)

  1. Find the load current. Single-phase: I = W ÷ (V × PF). Three-phase: I = W ÷ (1.732 × V × PF).
  2. Add 25 % for continuous loads (running three hours or more), such as EV chargers, heaters and lighting in stores.
  3. Pick the ampacity column. Start from the wire insulation column (60, 75 or 90 °C) and apply the temperature correction factor and the bundling factor for more than three current-carrying conductors.
  4. Check the terminals. The result may not exceed the ampacity in the column of the lowest-rated termination, usually 60 °C or 75 °C.
  5. Apply the small-conductor limits of 240.4(D): 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A.
  6. Check voltage drop and go up a size if the run is long.

What size wire for 15, 20, 30, 40, 50, 60 and 100 amps

What size wire for each breaker size (NEC Table 310.16, up to three current-carrying conductors, 86 °F, not continuous)
Breaker / loadCopper, 60 °C terminalsCopper, 75 °C terminalsAluminum, 60 °C terminalsAluminum, 75 °C terminals
15 A14 AWG14 AWG12 AWG12 AWG
20 A12 AWG12 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG8 AWG
40 A8 AWG8 AWG6 AWG8 AWG
50 A6 AWG8 AWG4 AWG6 AWG
60 A4 AWG6 AWG3 AWG4 AWG
70 A4 AWG4 AWG2 AWG3 AWG
80 A3 AWG4 AWG1 AWG2 AWG
100 A1 AWG3 AWG1/0 AWG1 AWG
125 A–1 AWG–2/0 AWG
150 A–1/0 AWG–3/0 AWG
200 A–3/0 AWG–250 kcmil
225 A–4/0 AWG–300 kcmil
300 A–350 kcmil–500 kcmil
400 A–600 kcmil–900 kcmil

The 60 °C column applies only up to 100 A (NEC 110.14(C)). Continuous loads, hot locations, bundled cables and long runs need a larger wire; use the calculator above. Dwelling services and feeders may use the smaller sizes allowed by 310.12.

Voltage drop formula for wire size

Single-phase: VD = 2 × K × I × L ÷ CM

Three-phase: VD = 1.732 × K × I × L ÷ CM

K is 12.9 Ω·cmil/ft for copper and 21.2 for aluminum, L the one-way length in feet and CM the conductor area in circular mils (12 AWG = 6,530; 10 AWG = 10,380; 6 AWG = 26,240; 1/0 = 105,600). Example: 20 A at 120 V over 50 ft of 12 AWG copper gives 2 × 12.9 × 20 × 50 ÷ 6,530 ≈ 3.95 V, or 3.3 %. That is above 3 %, so the calculator moves up to 10 AWG (2.1 %). For metric cables use the voltage drop calculator or the cable size calculator (mm²).

Wire ampacity chart (NEC Table 310.16)

Wire ampacity chart – NEC Table 310.16 (amps, 30 °C / 86 °F ambient, not more than three current-carrying conductors)
SizeCopper 60 °CCopper 75 °CCopper 90 °CAluminum 60 °CAluminum 75 °CAluminum 90 °C
14 AWG152025–––
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480
1000 kcmil455545615375445500

Source: NFPA 70 (NEC) Table 310.16, ampacities of insulated conductors rated up to 2000 V. 60 °C: TW, UF (and NM-B cable ampacity); 75 °C: THW, THWN, XHHW, USE; 90 °C: THHN, THWN-2, XHHW-2. 14–10 AWG are limited by 240.4(D).

Temperature and bundling correction

Table 310.16 assumes 86 °F (30 °C) and no more than three current-carrying conductors. Above 86 °F multiply by the correction factor, for example 0.91 for 90 °C wire at 96–104 °F, and 0.82 at 114–122 °F. With 4–6 current-carrying conductors in one raceway or cable use 80 %, with 7–9 use 70 % and with 10–20 use 50 %. The calculator applies both factors automatically.

Wire size questions

What size wire for 100 amp service?

For a 120/240 V single-phase dwelling service, NEC 310.12 lets you size the service conductors for 83 % of the rating: 4 AWG copper or 2 AWG aluminum for 100 A. For a 100 A feeder or circuit that is not a dwelling service, use Table 310.16 directly: 3 AWG copper or 1 AWG aluminum at 75 °C.

What size wire for 200 amp service?

Under NEC 310.12 a 200 A dwelling service needs 2/0 AWG copper or 4/0 AWG aluminum. Other 200 A feeders use Table 310.16 at 75 °C: 3/0 AWG copper or 250 kcmil aluminum.

What gauge wire for 30 amps?

10 AWG copper (or 8 AWG aluminum) for a 30 A circuit. 10 AWG copper is limited to a 30 A breaker by NEC 240.4(D). On long runs, check voltage drop and go up to 8 AWG if needed.

What size wire for 50 amps?

At 60 °C terminals, 6 AWG copper (55 A); at 75 °C terminals, 8 AWG copper (50 A). Aluminum needs 4 AWG at 60 °C or 6 AWG at 75 °C. Many 50 A range and EV circuits use 6 AWG copper.

What gauge wire for 20 amps?

12 AWG copper or 10 AWG aluminum. 12 AWG copper is limited to a 20 A breaker by NEC 240.4(D).

What is the difference between the 60 °C, 75 °C and 90 °C columns?

They are the insulation temperature ratings. You may start derating from the wire’s own column (for example 90 °C for THHN), but the final ampacity cannot exceed the column of the lowest-rated termination. Equipment rated 100 A or less often has 60 °C terminals unless marked 75 °C.

How much voltage drop is allowed?

The NEC informational notes recommend no more than 3 % on a branch circuit and 5 % total for feeder plus branch circuit. It is a recommendation for efficiency, not a mandatory rule, unless your local code or specification makes it one.