Calculation reviewed: 14 October 2026 · Engineering Desk Tools · How we check calculations
This Pt100 calculator converts RTD resistance to temperature and temperature to resistance for Pt100 and Pt1000 sensors. It uses the Callendar–Van Dusen equation from IEC 60751, the same curve used by transmitters and PLC RTD input cards.
Pt100 formula (Callendar–Van Dusen)
0 °C and above: R(t) = R₀ × (1 + A·t + B·t²)
Below 0 °C: R(t) = R₀ × (1 + A·t + B·t² + C·(t − 100)·t³)
A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷, C = −4.183 × 10⁻¹²
Resistance to temperature (0 °C and above): t = (−A + √(A² − 4·B·(1 − R/R₀))) ÷ (2·B)
R₀ is 100 Ω for a Pt100 and 1000 Ω for a Pt1000. The average slope between 0 and 100 °C is 0.385 Ω per °C for a Pt100 (alpha = 0.00385), which is a handy check in the field: every 1 Ω is roughly 2.6 °C.
Pt100 resistance table (IEC 60751)
Pt100 tolerance classes
How to use the Pt100 calculator
Choose the conversion direction and the sensor type (Pt100 or Pt1000), then enter the temperature in °C or the measured resistance in ohms. Select Calculate. When you check a sensor with a meter, measure at the sensor terminals or subtract the lead resistance, otherwise a 2-wire reading will show a higher temperature than the process.
Inputs and measurement basis
- Conversion. Choose whether you are entering a temperature or a measured resistance.
- Sensor type. Pt100 is 100 Ω at 0 °C and Pt1000 is 1000 Ω. Check the sensor label or data sheet.
- Temperature (°C) or resistance (Ω) for the selected conversion. Temperature in °C (−200 to 850) or resistance in Ω, matching the sensor type and conversion chosen above.
Method and interpretation
A platinum RTD changes resistance with temperature in a smooth, repeatable way described by the Callendar–Van Dusen equation. A Pt100 reads 100 Ω at 0 °C and about 138.5 Ω at 100 °C; a Pt1000 gives ten times those values. Above 0 °C the relationship is a quadratic, so the inverse has a closed form. Below 0 °C a fourth-order term is needed and the inverse is solved numerically.
For T ≥ 0 °C: R = R0 × (1 + A·T + B·T²). For T < 0 °C: R = R0 × (1 + A·T + B·T² + C·(T − 100)·T³). A = 3.9083×10⁻³, B = −5.775×10⁻⁷, C = −4.183×10⁻¹² (IEC 60751, α = 0.00385).
Valid from −200 °C to 850 °C for a platinum RTD with α = 0.00385. The result is the ideal nominal value; tolerance class (A, B, AA), self-heating, lead-wire resistance in 2-wire circuits and transmitter accuracy are not included. Enter resistance measured at the sensor, not the resistance of the wiring. Resistance to temperature below 0 °C is solved numerically.
Worked example
Calculated result: 138.5055 Ω. Nominal resistance of a standard platinum RTD. Tolerance class and wiring are not included.
2-wire, 3-wire and 4-wire RTD connections
The calculator gives the resistance of the sensing element itself. In a real installation the measured value also includes the resistance of the cable, and the wiring method decides how much of that reaches the reading.
Size of the 2-wire error. Near 0 °C a Pt100 changes by roughly 0.39 Ω per °C. Two leads of 0.5 Ω each add 1.0 Ω, which reads about 2.6 °C too high (1.0 ÷ 0.385). A Pt1000 changes ten times more per °C, so the same lead resistance causes about one tenth of the error.
How a 3-wire RTD reading is calculated
On a 3-wire sensor, two leads join the same end of the element and the third joins the other end. The instrument makes two resistance measurements: Ra through one lead, the element and the third lead, and Rb between the two leads that share the same end, which is the lead loop alone. The element resistance is Rt = Ra − Rb, and the temperature follows from the resistance-to-temperature mode of the calculator above.
Example. A Pt100 at 50 °C has an element resistance of 119.40 Ω. With three identical leads of 0.80 Ω each, Ra reads 121.00 Ω and Rb reads 1.60 Ω. Subtracting gives 119.40 Ω, which converts back to 50 °C. The leads have been removed from the result.
The method assumes the leads are equal. If one lead is 0.10 Ω longer than the others, about 0.10 Ω remains in the result, which is roughly 0.26 °C on a Pt100. That is why 3-wire is accurate for typical plant runs and 4-wire is used where the last fraction of a degree matters.
Check before trusting a reading. Confirm the connection type the transmitter or input card is configured for, measure the lead resistance with the sensor disconnected if you can, and check the terminal markings and wire colours on the sensor data sheet. Colour codes differ between manufacturers and standards, so do not rely on colour alone.
Common mistakes
Using a two-wire reading without allowing for lead resistance; mixing Pt100 and Pt1000; applying a thermocouple or NTC table; ignoring the sensor tolerance class; measuring resistance with the sensor still connected to a live loop.
Frequently asked questions
What is the resistance of a Pt100 at 0 °C and 100 °C?
A Pt100 is 100.00 Ω at 0 °C and 138.51 Ω at 100 °C. A Pt1000 is 1000.0 Ω and 1385.1 Ω.
What is the resistance of a Pt100 at 25 °C?
109.73 Ω. At 20 °C it is 107.79 Ω and at 50 °C it is 119.40 Ω.
How do you convert Pt100 resistance to temperature?
For 0 °C and above use t = (−A + √(A² − 4B(1 − R/100))) ÷ 2B with A = 3.9083e-3 and B = −5.775e-7. A quick estimate is (R − 100) ÷ 0.385. For 120 Ω the exact answer is 51.57 °C; the quick estimate gives 51.9 °C.
How many ohms per degree is a Pt100?
About 0.385 Ω per °C on average between 0 and 100 °C. A Pt1000 changes by about 3.85 Ω per °C.
What is the difference between Pt100 and Pt1000?
Both follow the same curve, but a Pt1000 has ten times the resistance. Lead resistance causes a ten times smaller error with a Pt1000, which makes it better for 2-wire connections and long cables.
What does the result mean?
The result is the nominal resistance or temperature for a standard platinum RTD. If a measured value differs from it, check wiring, lead resistance, sensor type and tolerance class before suspecting the sensor.
Can I connect a 3-wire Pt100 to a 2-wire input?
Usually yes. Fit a link between the two terminals of the same colour on the sensor side, or leave the third lead unused, but the input will then measure lead resistance as temperature. Set the instrument for the connection you actually wired, and keep leads short or use a 4-wire arrangement when accuracy matters.
How do I calculate temperature from a 3-wire RTD?
Measure or read the resistance through the element and the two leads (R_a) and the lead loop alone (R_b), subtract to get the element resistance, then enter that value in the calculator’s resistance-to-temperature mode. Most transmitters and PLC input cards do this automatically when configured for 3-wire. The result assumes the three leads have equal resistance.
How do I check a Pt100 with a multimeter?
Disconnect the sensor from the instrument and measure across the element terminals. At about 20 °C a Pt100 should read near 107.8 Ω; the calculator gives the expected value for your temperature. On a 3-wire sensor, the two same-colour leads should read close to 0 Ω between them. A meter has its own lead error, so subtract the test lead resistance on low readings.
Related tools and records
Use related calculations with consistent units, periods and equipment scope.
Embed this calculator
Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.