E•ENGINEERING
DESK TOOLS

Engineering tools

42 tools · instant results

ELECTRICAL

Transformer Size Calculator – kVA Rating & Low Voltage Sizing

Estimate the required transformer kVA, the next standard rating and the rated secondary current.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

Load kVA = kW / PF. Required kVA = load kVA × (1 + margin / 100). Rated secondary current = standard kVA × 1000 / (√3 × V) for three-phase, or kVA × 1000 / V for single-phase.

Use maximum demand, not the sum of all nameplates, unless every load can run together. The standard ratings listed (25 to 3150 kVA) are common values; availability varies by region and manufacturer. Motor starting, harmonics, ambient temperature, cooling class, impedance and loading policy can change the right choice.

Method: standard dimensional arithmetic; equation and input units shown above.

Calculation reviewed: 14 October 2026 · Engineering Desk Tools · How we check calculations

This transformer size calculator turns your maximum load in kW into the kVA rating you need, picks the next standard size and gives the rated secondary current. Below the calculator you will find a standard size table and a method for small low voltage transformers (12 V and 24 V).

Transformer sizing formula

Load kVA = kW ÷ PF

Required kVA = load kVA × (1 + spare capacity % ÷ 100)

Three-phase from current: kVA = 1.732 × V × I ÷ 1000

Single-phase from current: kVA = V × I ÷ 1000

Example: a 100 kW maximum demand at 0.85 power factor is 117.6 kVA. With 20 % spare capacity the need is 141 kVA, so the next standard size is 160 kVA. At 400 V its rated secondary current is 231 A.

Standard transformer kVA sizes and full-load current

Three-phase distribution transformers. Common IEC ratings; availability varies by region.
RatingFull-load current 400 V415 V480 VMax load at PF 0.85 with 20 % spare
25 kVA36.1 A34.8 A30.1 A17.7 kW
50 kVA72.2 A69.6 A60.1 A35.4 kW
63 kVA90.9 A87.6 A75.8 A44.6 kW
100 kVA144 A139 A120 A70.8 kW
125 kVA180 A174 A150 A88.5 kW
160 kVA231 A223 A192 A113 kW
200 kVA289 A278 A241 A142 kW
250 kVA361 A348 A301 A177 kW
315 kVA455 A438 A379 A223 kW
400 kVA577 A556 A481 A283 kW
500 kVA722 A696 A601 A354 kW
630 kVA909 A876 A758 A446 kW
800 kVA1,155 A1,113 A962 A567 kW
1,000 kVA1,443 A1,391 A1,203 A708 kW
1,250 kVA1,804 A1,739 A1,504 A885 kW
1,600 kVA2,309 A2,226 A1,925 A1,133 kW
2,000 kVA2,887 A2,782 A2,406 A1,417 kW
2,500 kVA3,608 A3,478 A3,007 A1,771 kW

Low voltage transformer size calculator (12 V and 24 V)

The calculator above is for distribution transformers from 25 kVA. Small low voltage transformers for landscape lighting, LED strips and control circuits are rated in VA. Size them like this:

  1. Add up the watts (or VA) of every lamp or device on the transformer.
  2. Multiply by 1.25 so the transformer runs at no more than about 80 % of its rating.
  3. Choose the next size up, and check the secondary current against the cable and fuse.
Low voltage transformer sizing at 80 % loading. Common landscape and LED transformer sizes; check the range of your supplier.
Total loadRequired (load × 1.25)Next common sizeCurrent at 12 VCurrent at 24 V
60 W75 VA75 VA5.00 A2.50 A
100 W125 VA150 VA8.33 A4.17 A
150 W187.5 VA200 VA12.5 A6.25 A
200 W250 VA300 VA16.7 A8.33 A
300 W375 VA600 VA25.0 A12.5 A
450 W562.5 VA600 VA37.5 A18.8 A
600 W750 VA900 VA50.0 A25.0 A
900 W1125 VA1200 VA75.0 A37.5 A

For control transformers that feed contactor and relay coils, the inrush VA when coils pull in can be several times the sealed VA. Manufacturers give a sizing method that adds sealed VA and inrush VA at the allowed voltage dip, so use their selection table rather than the 80 % rule alone.

How to use the Transformer Size calculator

Choose single-phase or three-phase, enter the maximum load in kW (maximum demand, not the sum of all nameplates), the load power factor, the spare capacity you want for growth and the secondary voltage. Select Calculate to see the required kVA, the next standard rating, the loading at your stated load and the rated secondary current.

Inputs and measurement basis

Method and interpretation

A transformer is limited by current, and so by kVA rather than kW. The load in kW is therefore converted to apparent power with the power factor. A growth margin is added and the next standard rating is chosen. The rated secondary current follows from the kVA and the secondary voltage.

Load kVA = kW / PF. Required kVA = load kVA × (1 + margin / 100). Rated secondary current = standard kVA × 1000 / (√3 × V) for three-phase, or kVA × 1000 / V for single-phase.

Use maximum demand, not the sum of all nameplates, unless every load can run together. The standard ratings listed (25 to 3150 kVA) are common values; availability varies by region and manufacturer. Motor starting, harmonics, ambient temperature, cooling class, impedance and loading policy can change the right choice.

Worked example

InputExample value
SupplyThree-phase
Maximum load (kW)200
Load power factor (decimal, up to 1)0.8
Spare capacity for growth (%)20
Secondary voltage (V)400

Calculated result: 300 kVA required. Confirm impedance, starting duty, harmonics, temperature and availability with the supplier before purchase.

Common mistakes

Adding every motor nameplate when the loads never run together; leaving out the margin for growth and motor starting; mixing line-to-neutral with line-to-line voltage; forgetting that a larger transformer has a higher fault level and different losses.

Frequently asked questions

How do I calculate transformer size?

Divide the maximum load in kW by the power factor to get kVA, add a margin for growth (often 20–25 %), then choose the next standard kVA rating. For example, 200 kW at 0.8 PF is 250 kVA; with 20 % spare it is 300 kVA, so choose 315 kVA.

What size transformer do I need for 100 kW?

At 0.85 power factor, 100 kW is 117.6 kVA. With 20 % spare capacity that is 141 kVA, so a 160 kVA transformer. At 0.8 PF and 20 % spare you need 150 kVA, so still 160 kVA.

How many amps is a 500 kVA transformer?

The full-load secondary current is 722 A at 400 V, 696 A at 415 V and 601 A at 480 V three-phase.

How do you size a low voltage lighting transformer?

Add the total watts of the lamps, multiply by 1.25 and choose the next transformer size. For 240 W of 12 V landscape lights you need at least 300 VA, and the secondary current is 20 A.

Why are transformers rated in kVA instead of kW?

Transformer heating depends on current and voltage, not on the power factor of the load. The kVA rating applies to any load power factor.

Can a transformer run at 100 % load?

Yes, a transformer is designed to carry its rated kVA continuously at rated ambient temperature. Leaving 20–25 % spare gives room for growth, hot weather and motor starting.

What does the result mean?

The result is the kVA the transformer must supply with margin, the next standard rating above it and that rating’s secondary current. A loading close to 100 percent leaves little room for growth or motor starting.

Related tools and records

Use related calculations with consistent units, periods and equipment scope.

Embed this calculator

Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.