kVA to Amps Calculator – Single & Three Phase

Convert apparent power into line current for a single-phase or balanced three-phase supply.

READY FOR YOUR DATA

Enter your values, then select Calculate.

Formula & assumptions

I = S × 1000 / (√3 × V) for three-phase; I = S × 1000 / V for single-phase.

Three-phase voltage is line-to-line RMS. This is load current, not a cable size or breaker recommendation. kVA is apparent power; power factor is not needed.

Calculation reviewed: 4 October 2026 · Engineering Desk Tools · How we check calculations

kVA to amps formula

Three-phase: I (A) = kVA × 1000 ÷ (√3 × VL-L)

Single-phase: I (A) = kVA × 1000 ÷ V

√3 is about 1.732. For example, a 500 kVA transformer at 400 V three-phase has a full-load current of 500 × 1000 ÷ (1.732 × 400) = 722 A. At 480 V the same transformer carries 601 A.

Amps to kVA formula

Three-phase: kVA = √3 × V × I ÷ 1000

Single-phase: kVA = V × I ÷ 1000

A three-phase load drawing 100 A at 415 V is 1.732 × 415 × 100 ÷ 1000 = 71.9 kVA. To get kW instead of kVA, multiply by the power factor or use the amps to kW calculator.

kVA to amps chart – three-phase

Full-load line current for a balanced three-phase load, line-to-line voltage.
kVA208 V400 V415 V480 V
15 kVA41.6 A21.7 A20.9 A18.0 A
30 kVA83.3 A43.3 A41.7 A36.1 A
45 kVA125 A65.0 A62.6 A54.1 A
75 kVA208 A108 A104 A90.2 A
100 kVA278 A144 A139 A120 A
112.5 kVA312 A162 A157 A135 A
150 kVA416 A217 A209 A180 A
225 kVA625 A325 A313 A271 A
300 kVA833 A433 A417 A361 A
500 kVA1,388 A722 A696 A601 A
750 kVA2,082 A1,083 A1,043 A902 A
1000 kVA2,776 A1,443 A1,391 A1,203 A
1500 kVA4,164 A2,165 A2,087 A1,804 A
2000 kVA5,551 A2,887 A2,782 A2,406 A
2500 kVA6,939 A3,608 A3,478 A3,007 A

kVA to amps chart – single-phase

Full-load current for a single-phase load.
kVA120 V230 V240 V
1 kVA8.33 A4.35 A4.17 A
3 kVA25.0 A13.0 A12.5 A
5 kVA41.7 A21.7 A20.8 A
10 kVA83.3 A43.5 A41.7 A
15 kVA125 A65.2 A62.5 A
25 kVA208 A109 A104 A
37.5 kVA312 A163 A156 A
50 kVA417 A217 A208 A
75 kVA625 A326 A312 A
100 kVA833 A435 A417 A

These are load currents. Cable size, breaker rating and transformer protection depend on installation method, ambient temperature and the applicable wiring rules.

kVA vs kW

kVA is apparent power, the product of voltage and current. kW is real power, the part that does useful work: kW = kVA × power factor. Transformers and generators are rated in kVA because their heating depends on current, whatever the power factor of the load. To convert a kW load, use the kW to amps calculator, which includes power factor.

How to use the kVA to Amps calculator

Choose single-phase or three-phase, enter the apparent power in kVA and the supply voltage, then select Calculate. For three-phase, enter the line-to-line voltage. Power factor is not needed, because kVA is already apparent power.

Inputs and measurement basis

Method and interpretation

Apparent power differs from active power. A kVA rating describes voltage multiplied by current, while a kW value also includes the effect of power factor. Select the supply arrangement before comparing results. In a balanced three-phase calculation the voltage is measured between phases, so a 400 V entry is not the 230 V phase-to-neutral reading.

I = S × 1000 / (√3 × V) for three-phase; I = S × 1000 / V for single-phase.

Three-phase voltage is line-to-line RMS. This is load current, not a cable size or breaker recommendation. kVA is apparent power; power factor is not needed.

Worked example

InputExample value
SupplyThree-phase
Apparent power (kVA)25
Voltage (V)400

Calculated result: 36.0844 A. Estimated line current

Common mistakes

Using kW as though it were kVA; entering phase-to-neutral voltage in the three-phase formula; treating calculated operating current as a protective-device rating.

Frequently asked questions

How do you convert kVA to amps?

For three-phase, multiply kVA by 1000 and divide by 1.732 × the line-to-line voltage. For single-phase, multiply kVA by 1000 and divide by the voltage. Power factor is not needed.

How many amps is 1 kVA?

1 kVA is 4.17 A at 240 V single-phase, 4.35 A at 230 V and 8.33 A at 120 V. At 400 V three-phase it is 1.44 A per line, and 1.20 A at 480 V.

How many amps is a 1000 kVA transformer?

At 400 V three-phase the full-load current is about 1,443 A. At 415 V it is 1,391 A and at 480 V it is 1,203 A.

How do you convert amps to kVA?

Three-phase: kVA = 1.732 × volts × amps ÷ 1000. Single-phase: kVA = volts × amps ÷ 1000.

Why is power factor not used for kVA to amps?

kVA is apparent power, which already includes the effect of power factor. Power factor is only needed when you start from kW.

What does the result mean?

The result is the line current the load draws at the entered apparent power and voltage. Use it to compare against the equipment nameplate or a clamp-meter reading, not to select a cable or breaker.