kVA to amps formula
Three-phase: I (A) = kVA × 1000 ÷ (√3 × VL-L)
Single-phase: I (A) = kVA × 1000 ÷ V
√3 is about 1.732. For example, a 500 kVA transformer at 400 V three-phase has a full-load current of 500 × 1000 ÷ (1.732 × 400) = 722 A. At 480 V the same transformer carries 601 A.
Amps to kVA formula
Three-phase: kVA = √3 × V × I ÷ 1000
Single-phase: kVA = V × I ÷ 1000
A three-phase load drawing 100 A at 415 V is 1.732 × 415 × 100 ÷ 1000 = 71.9 kVA. To get kW instead of kVA, multiply by the power factor or use the amps to kW calculator.
kVA to amps chart – three-phase
kVA to amps chart – single-phase
These are load currents. Cable size, breaker rating and transformer protection depend on installation method, ambient temperature and the applicable wiring rules.
kVA vs kW
kVA is apparent power, the product of voltage and current. kW is real power, the part that does useful work: kW = kVA × power factor. Transformers and generators are rated in kVA because their heating depends on current, whatever the power factor of the load. To convert a kW load, use the kW to amps calculator, which includes power factor.
How to use the kVA to Amps calculator
Choose single-phase or three-phase, enter the apparent power in kVA and the supply voltage, then select Calculate. For three-phase, enter the line-to-line voltage. Power factor is not needed, because kVA is already apparent power.
Inputs and measurement basis
- Supply. Use three-phase for a balanced three-phase supply and single-phase for a two-wire circuit.
- Apparent power (kVA). Apparent power from the nameplate or supply rating, in kVA.
- Voltage (V). Supply voltage; line-to-line for three-phase. The value must be greater than zero.
Method and interpretation
Apparent power differs from active power. A kVA rating describes voltage multiplied by current, while a kW value also includes the effect of power factor. Select the supply arrangement before comparing results. In a balanced three-phase calculation the voltage is measured between phases, so a 400 V entry is not the 230 V phase-to-neutral reading.
I = S × 1000 / (√3 × V) for three-phase; I = S × 1000 / V for single-phase.
Three-phase voltage is line-to-line RMS. This is load current, not a cable size or breaker recommendation. kVA is apparent power; power factor is not needed.
Worked example
Calculated result: 36.0844 A. Estimated line current
Common mistakes
Using kW as though it were kVA; entering phase-to-neutral voltage in the three-phase formula; treating calculated operating current as a protective-device rating.
Frequently asked questions
How do you convert kVA to amps?
For three-phase, multiply kVA by 1000 and divide by 1.732 × the line-to-line voltage. For single-phase, multiply kVA by 1000 and divide by the voltage. Power factor is not needed.
How many amps is 1 kVA?
1 kVA is 4.17 A at 240 V single-phase, 4.35 A at 230 V and 8.33 A at 120 V. At 400 V three-phase it is 1.44 A per line, and 1.20 A at 480 V.
How many amps is a 1000 kVA transformer?
At 400 V three-phase the full-load current is about 1,443 A. At 415 V it is 1,391 A and at 480 V it is 1,203 A.
How do you convert amps to kVA?
Three-phase: kVA = 1.732 × volts × amps ÷ 1000. Single-phase: kVA = volts × amps ÷ 1000.
Why is power factor not used for kVA to amps?
kVA is apparent power, which already includes the effect of power factor. Power factor is only needed when you start from kW.
What does the result mean?
The result is the line current the load draws at the entered apparent power and voltage. Use it to compare against the equipment nameplate or a clamp-meter reading, not to select a cable or breaker.
Related tools and records
Use related calculations with consistent units, periods and equipment scope.
Embed this calculator
Copy this code into your website. The calculator stays free, with a visible attribution link. Visitors can use it without signing up.