kW to amps formula
Three-phase AC: I (A) = kW × 1000 ÷ (√3 × VL-L × PF)
Single-phase AC: I (A) = kW × 1000 ÷ (V × PF)
DC: I (A) = kW × 1000 ÷ V
Example: a 15 kW three-phase load at 400 V and a power factor of 0.85 draws 15,000 ÷ (1.732 × 400 × 0.85) = 25.5 A. The same load at 480 V draws 21.2 A.
kW to amps chart – 208, 480, 120 and 230 V
For 400 V and 415 V, and for motors rated in shaft kW, see the motor table further down this page.
3 phase amperage calculator: quick answers
Use this table as a three phase amp calculator for common sizes. Values are line current at 0.85 power factor. For a different power factor, use the calculator above or multiply by 0.85 ÷ your PF.
kW to amps for heaters and EV chargers (power factor 1)
Resistive heaters, kettles, immersion heaters and most EV chargers run close to unity power factor, so the current is simply I = kW × 1000 ÷ V. A 7.2 kW EV charger on 240 V draws 30 A.
kW to amps at 440 V three-phase
I = kW × 1000 ÷ (1.732 × 440 × PF)
440 V is common on ships and in some plants and older 60 Hz systems. At 0.85 power factor, 10 kW draws 15.4 A, 37 kW draws 57.1 A and 75 kW draws 116 A per line.
How to use the kW to Amps calculator
Choose single-phase or three-phase, enter the electrical input power in kW, the supply voltage and the power factor, then select Calculate. For a motor rated in shaft kW, first divide by the motor efficiency to get input power.
Inputs and measurement basis
- Supply. Use three-phase for a balanced three-phase supply and single-phase for a two-wire circuit.
- Electrical input power (kW). Electrical input power in kW. A motor nameplate kW is usually shaft output, so divide by efficiency first.
- Supply voltage (V). Supply voltage; line-to-line for three-phase. The value must be greater than zero.
- Power factor (decimal, up to 1). Power factor as a decimal such as 0.85, not 85. The allowed maximum is 1. The value must be greater than zero.
Method and interpretation
The entered power is active electrical input. A motor nameplate often gives shaft output, which is a different quantity. If shaft power is the only available value, divide it by the motor efficiency to obtain an input estimate before using this tool. Power factor and efficiency are separate parameters; neither should be inferred from the other.
Single-phase: I = kW × 1000 / (V × PF). Three-phase: I = kW × 1000 / (√3 × V × PF).
Use RMS voltage and a power factor greater than 0 and up to 1. For balanced three-phase supplies, enter line-to-line voltage. Power is electrical input, not motor shaft output; convert shaft power to input power using motor efficiency first. This result is load current, not a cable or breaker size.
Worked example
Calculated result: 24.5507 A. Estimated AC line current
kW to amps for common motor and load sizes
Three-phase line current for typical ratings, calculated with this page's method at a power factor of 0.85. The first two columns treat the kW figure as electrical input power. The last column treats it as shaft output and assumes a motor efficiency of 90 percent, so the input power is the shaft rating divided by 0.9.
A 3.7 kW rating is the metric equivalent of a 5 hp motor (5 × 0.7457 = 3.73 kW), and 3 kW is a common rating for small pumps and fans. If your motor is listed in hp, convert it with the HP to kW calculator and then read the row above.
These are running-current estimates for learning and planning. Nameplate full-load current, starting current, service factor and cable or protection sizing come from the equipment documentation and the applicable rules. The power factor and efficiency of a real motor change with load, so replace 0.85 and 90 percent with the values for your motor.
Common mistakes
Entering power factor as 85 instead of 0.85; using motor output power without efficiency correction; assuming every motor of the same size draws exactly the calculated current.
Frequently asked questions
How much kW is 1 amp?
It depends on the voltage. 1 A at 230 V single-phase is 0.23 kW at power factor 1. 1 A per line at 400 V three-phase is 0.59 kW at 0.85 power factor, and 0.71 kW at 480 V.
How many amps is 10 kW 3 phase?
At 0.85 power factor: 17.0 A at 400 V, 16.4 A at 415 V, 15.4 A at 440 V and 14.2 A at 480 V. At power factor 1 and 400 V it is 14.4 A.
What is 15 kW to amps?
15 kW three-phase at 0.85 power factor is 25.5 A at 400 V, 24.6 A at 415 V and 21.2 A at 480 V. On 230 V single-phase it is 76.7 A at 0.85 PF, or 65.2 A for a resistive load.
How many amps is 7.2 kW?
A 7.2 kW EV charger on 240 V single-phase draws 30 A (31.3 A at 230 V). A 7.2 kW three-phase load at 400 V and 0.85 power factor draws 12.2 A per line.
How many amps is 9 kW?
9 kW on 240 V single-phase at power factor 1 is 37.5 A (39.1 A at 230 V). Three-phase at 400 V and 0.85 PF it is 15.3 A per line.
Is there a separate 3 phase amperage calculator for kVA?
Yes. If your rating is in kVA, such as a transformer or generator, use the kVA to amps calculator. Power factor is not needed for that conversion. To change kVA to kW first, use the kVA to kW calculator.
How do you convert kW to amps?
For three-phase, divide kW × 1000 by 1.732 × line voltage × power factor. For single-phase, divide kW × 1000 by voltage × power factor. For DC, divide kW × 1000 by voltage.
How many amps is 1 kW?
At a power factor of 0.85, 1 kW is about 1.70 A at 400 V three-phase, 1.42 A at 480 V three-phase and 5.12 A at 230 V single-phase. At unity power factor, 1 kW at 230 V is 4.35 A.
What does the result mean?
The result is the estimated line current for the entered electrical input power, voltage and power factor. Compare it with the nameplate or a measured value; protection and cable sizing need separate rules.
What is the current for a 7.5 kW motor at 400 V?
If 7.5 kW is the electrical input power at a power factor of 0.85, the line current is about 12.74 A. If 7.5 kW is the shaft rating and the motor is 90 percent efficient, the input power is 8.33 kW and the current is about 14.15 A. Confirm against the nameplate.
What is the current for a 3.7 kW (5 hp) motor at 400 V?
At 400 V three-phase and a power factor of 0.85, a load drawing 3.7 kW of electrical input power takes about 6.28 A. If 3.7 kW is the motor’s shaft rating and its efficiency is 90 percent, the input power is 4.11 kW and the current is about 6.98 A. For a 6.6 kW load, scale the first figure by 6.6 ÷ 3.7.
Why does the kW to amps result differ from the motor nameplate?
The nameplate usually gives shaft power and a full-load current measured at rated conditions, including the motor’s real efficiency and power factor. A generic calculation with an assumed power factor will not match exactly. Use the nameplate or a measurement as the reference and the calculator as a cross-check.